Who this guide is for
This guide is for HVAC contractors and duct shops that buy dampers and access doors in volume for projects, rather than one at a time from a local wholesaler. Dampers and doors are small lines on a drawing and big lines on a schedule, and they are the items most often ordered with a missing detail: no size shape, no operation, no thought for insulation. The range we supply is on the dampers page and the access doors and accessories page. This guide covers what to write on the schedule so the quote matches what you need.
Which damper goes where
Start with the job each damper has to do, because the type follows from that.
- Balancing (regulating) dampers go in branches and at terminal take-offs, so the commissioning engineer can set the airflow in each leg. On our balancing damper the blade is set steplessly from 0 to 90 degrees and locked by a screw. Iris dampers do the same job in a compact round body, and the iris version with a setting scale lets the installer read the position.
- Backdraft (non-return) dampers let air go one way only. They sit on extract and exhaust runs, such as toilet, kitchen and fan outlets, to stop outside air and smells coming back down the duct. A spring-loaded non-return version is also in the range.
- Airtight shut-off dampers close a branch off completely, for zones that are switched off or isolated for part of the day.
- Multi-vane dampers handle the larger sizes.
- Motorised and air-operated dampers are for automatic control: the round motorised damper has the electric actuator mounted on the body, and the air-operated damper is moved by an air cylinder.
A balancing damper that has to close tight is the wrong part, and a shut-off damper used for balancing will not hold a setting well. Write the duty on the schedule, not just the word damper. Fire and smoke dampers are a separate subject because ratings, approvals and installation rules apply, so they are covered in our guide on fire and smoke damper integration and not repeated here.
What to put on the schedule for each damper
Duct size and shape
Give the round diameter for every line. Our standard round sizes run from Ø80 to Ø500, with other diameters made on request. The listed damper range is round. If your job has rectangular dampers, write width x height and tell us at the take-off stage, and we confirm what can be quoted before you plan around it. See the rectangular duct and fittings page for the rectangular range.
Blade arrangement
Where a damper has more than one blade, the arrangement matters. In an opposed blade damper, adjacent blades turn in opposite directions, which gives a steadier relationship between blade angle and airflow, so it suits balancing and modulating control. In a parallel blade damper all blades turn the same way, which suits two-position (open or closed) duty and mixing. If your project specification names one, copy it onto the schedule. If it does not, tell us the duty and we confirm the blade arrangement on the quotation.
Material, gauge and coating
Dampers are galvanised steel as standard, with stainless steel welded dampers on request. On the balancing dampers the sheet thickness runs from 0.5 mm in the small sizes to 0.8 mm at Ø500, with the exact figure confirmed per line. For backdraft dampers, one recent export order was 1.0 mm galvanised Z80 with a rubber seal, slipped straight into Ø150, Ø200 and Ø250 duct. Seals are EPDM rubber, fixed in place on the spigot so they do not slide off during assembly. Write the material, the zinc coating (Z80 or Z275) and the seal type on every line, as the bulk buying take-off checklist explains for fittings in general.
Operation
State how each damper is operated. Hand setting is the standard. For automatic control you have three routes: a motorised damper with the electric actuator on the body, an air-operated damper, or an actuator-ready version, which we confirm at quotation against the actuator you plan to use. If you do not know yet, say so, because the answer changes the damper body. Mixing hand-set and actuated dampers on one schedule without saying which is which is the most common reason a quote needs a second round.
Insulation
On insulated systems, say whether the damper is fitted into pre-insulated duct or into duct that will be lagged on site. The range includes pre-insulated dampers and insulated motorised dampers, listed on the pre-insulated duct and fittings page. If you are lagging on site, give the insulation thickness, because the handle, locking screw or actuator has to clear the insulation and stay reachable after it goes on.
Leakage: what the test standards cover
Two test standards come up on damper schedules. EN 1751 sets out the aerodynamic test methods for dampers and valves in air distribution systems, and classifies both leakage past a closed damper and leakage through its casing. AMCA 500-D, from the Air Movement and Control Association, sets laboratory methods of testing dampers for rating, covering air leakage, pressure drop, dynamic closure and operating torque. Both are test methods, not a pass mark: they say how a damper is tested and how results are reported.
So if a specification says a damper must meet a class, write the standard, the class and the test pressure on the schedule. We do not publish a leakage class on our damper pages, so we confirm on the quotation what can be offered for your requirement rather than assume it. For leakage of the duct system itself, see our guide on duct air leakage classes.
Access doors: what to specify
Access doors go wherever something in the duct has to be inspected, reset or cleaned: next to dampers, coils and other equipment, and at intervals along long runs. Fire and smoke dampers need access in particular. In the US, NFPA 90A requires fire dampers to be maintained under NFPA 80 and smoke dampers under NFPA 105, and maintenance is not practical without a door to reach them. In Europe, EN 12097 sets requirements for access openings and panels so ductwork can be cleaned and serviced. Local codes differ and win over any general guide, so check the one that applies to your project.
For each access door, write:
- Size. Our access doors for round duct are sized per diameter. The FAD and CAD doors have an oval panel held by two quick-release knobs. Check that the opening is large enough for the job: reaching a damper link or cleaning a coil needs a larger opening than a visual check.
- Duct type. Round or rectangular, and the diameter or width x height. The listed access doors are for round duct, so tell us early if you also need doors for rectangular duct.
- Fixing and opening. Say whether you want a door that stays attached or a panel that comes off completely, and whether the door needs a tool or opens by hand. Quick-release knobs suit frequent access.
- Insulation. Say whether the duct is lagged and the thickness, so the door suits the build-up.
- Sealing. Say whether the door is on a system with a leakage class. Gaskets, hinges and options for each size are confirmed on the quotation.
Plan the door positions before you order. A door that lands behind a beam or above a fixed ceiling cannot be used, however good it is, and fixing it on site costs more than the door. Where the duct needs a flexible connection, the range also includes firestop flexible connections, round and rectangular.
What to send us to quote
Send one row per item and size. The table shows the columns we need.
Add the leakage standard or class if the specification names one, the delivery port, and whether the goods ship alone or with a machine order. Quantity is quoted per order, and if you buy monthly, give the monthly figure as well so we can plan the carton packing. Dampers do not nest, so they take their own carton space and are included in the packing plan when we quote. There is no price list, because the price depends on size, material, operation and quantity on each line.
Common mistakes
- Writing "damper, 200" with no duty, so the supplier cannot tell a balancing damper from a shut-off damper.
- Leaving out how the damper is operated until after the order.
- Ordering dampers for insulated duct without the insulation thickness.
- Quoting a test standard without the class or pressure, which says nothing a supplier can price.
- Placing access doors on the drawing without checking that someone can reach them.
Send your damper and door schedule for a quote in 12 hours →
Taokron supplies these dampers and doors. Catalogue figures are confirmed on the quotation for your order.
FAQ
What do I send to get dampers and access doors quoted?
Your schedule or take-off as a list, Excel, PDF or a photo of the drawing schedule. For each line give the item, duct diameter (or width x height for rectangular), quantity per order, material and coating, how it is operated (hand setting or actuator), and any insulation. Add the delivery port and whether the goods ship alone or with a machine order.
Which damper types are in the Taokron range?
Backdraft (non-return) dampers, balancing (regulating) dampers, iris dampers, airtight shut-off dampers, multi-vane dampers, spring-loaded non-return dampers, air-operated dampers and motorised dampers with an electric actuator on the body. Stainless steel welded and pre-insulated versions are also listed. Standard round sizes run from Ø80 to Ø500.
Can a damper take an actuator?
Hand setting is standard. Actuator-ready versions are confirmed at quotation, so tell us the actuator you plan to fit, or ask for the motorised version with the electric actuator mounted on the body.
What leakage class do your dampers meet?
We do not publish a leakage class on the product pages. If your specification calls up a test standard or class, put it on the schedule and we confirm on the quotation what can be offered. EN 1751 and AMCA 500-D are test methods for dampers, so they describe how a damper is tested, not what a given damper achieves.
Do you supply fire and smoke dampers?
Fire and smoke dampers have their own rules for ratings, approvals and installation, covered in our guide on fire and smoke damper integration. Send your requirement and the rating your project needs and we confirm what can be quoted before you rely on it.
Is there a price list for dampers and access doors?
No. Each line is quoted from your take-off by size, material, operation and quantity, and the quotation is per order quantity.