Who this guide is for
This guide is for HVAC contractors and duct shops that buy air terminals for projects: the grilles, diffusers and valves that sit at the end of the duct. They are the most visible part of the system and the part most often ordered from a schedule with gaps: a size with no note on whether it is the neck or the face, a type with no duty, a finish with no colour. The range we supply is on the grilles, diffusers and air valves page. This guide covers what to write on the schedule so the quote matches what you need.
Start with the duty: supply, return or exhaust
Every terminal has one of three jobs, and the job decides the type.
- Supply. The air comes out and has to be thrown into the room in the right pattern. Square ceiling diffusers throw the air 1, 2, 3 or 4 ways from a removable inner cone. Supply grilles with adjustable blades suit walls and bulkheads. Round supply air valves fit straight into round duct for small rooms, toilets and cabins.
- Return. The air is drawn in, so the pattern matters much less than free area and a face that does not whistle. Eggcrate grilles are the usual return.
- Exhaust. Round exhaust air valves serve toilets and small rooms, set by turning the centre disc.
Mark the duty on every line of the schedule. A supply diffuser and a return grille can look alike on a drawing and are not interchangeable in use. If the same size appears as both, give them separate tags.
The types we supply, and where each goes
If your project needs a type that is not in this table, such as a linear slot diffuser or a jet nozzle, tell us at the take-off stage and we confirm what can be quoted before you plan around it.
Neck size or face size
This is the most common gap on a schedule. The neck size is the size of the connection where the terminal joins the duct or the adapter. The face size is the visible size in the ceiling or wall. They are different numbers, and on a ceiling diffuser the face is larger than the neck. Performance data is normally given against the neck, while the architect's reflected ceiling plan is drawn to the face and the ceiling module.
So write both. A line such as "SD-03, 4-way, neck 300 x 300, face 600 x 600" cannot be misread. If you give only one number, say which it is. Our diffusers and grilles are made to the size on your schedule, so write width x height (or A x B for diffusers) and the quantity per size.
Material, finish and colour
- Material. Diffusers are aluminium or stainless steel. Supply and eggcrate grilles are aluminium. The opposed blade damper behind a face is cold-rolled steel and the square-to-round adapter is galvanised steel. If the area is wet or washed down, ask us about stainless steel, and write the environment on the schedule.
- Finish and colour. Write the finish and colour for every line, and a reference if the architect has named one. We do not list a finish chart on the product page, so we confirm on the quotation what can be offered for your colour. Do not leave it for after the order, because a standard finish and a custom colour are different production runs.
- Frame edge. Supply grilles come with a 23 or 32 mm frame edge. Choose it to suit the wall or bulkhead detail.
- Gauges and seals. Gauges, coatings and seals are confirmed per line on the quotation.
Volume control behind the face
Behind a diffuser or grille you can fit an opposed blade damper to set the air volume, and a square-to-round adapter to connect it to round duct. In an opposed blade damper adjacent blades turn in opposite directions, which gives a steadier relationship between blade angle and airflow, so it suits balancing. Decide early whether each terminal gets a damper, because it changes the neck depth and the order. The air balancer needs a way to reach it, and the diffuser's removable inner cone helps there. See our air balancing guide for how the setting is made on site. The separate dampers range is on the dampers page.
Mounting and fixing
Say how each terminal is fixed, because it sets the frame style. The usual questions are:
- Is the terminal fitted in a ceiling grid, a plasterboard ceiling or an exposed duct side?
- Is the fixing visible or concealed?
- Is it connected directly to the duct, to a flexible connection or to a plenum box? Where a plenum box or acoustic treatment is involved, see the silencers and plenum boxes page.
- Does the ceiling void have room for the neck and damper?
The listed range is made to the sizes on your schedule, and fixing details are confirmed on the quotation for your ceiling type. For access to anything behind the face, such as a damper link, plan the access doors at the same time, which our access doors and accessories page covers.
Throw, noise and pressure drop: how terminals are selected
A terminal is selected on three numbers together, not one. Each is tested to a published method, so the numbers from different suppliers can be compared like for like only if they used the same method.
Throw
The ASHRAE Handbook defines throw as the distance from the centreline of an outlet to a point in the mixed airstream where the velocity has dropped to a stated terminal velocity, with 50, 100, 150 or 200 fpm given as examples, and it attributes the definition to ASHRAE Standard 70. So a throw figure means nothing without its terminal velocity. If the designer gives you a throw, write the terminal velocity next to it on the schedule. For a ceiling diffuser the pattern setting (1 to 4 way) changes the throw, so the pattern belongs on the line too.
Noise: NC and NR
The sound a terminal makes is judged in the room, using a single-number rating. Two systems are in common use: NC (noise criterion), introduced by Leo Beranek in 1957, and NR (noise rating), whose curves were first published in an ISO recommendation in 1971. NR is more common in Europe, and NC is more common in the USA. Each number stands for a curve of maximum sound levels across octave bands, so a higher number allows more noise. If the specification gives a room limit as NC or NR, copy it onto the schedule with the airflow for each terminal, and note which system it uses. A terminal that is quiet at low airflow can be loud at the airflow it has on the day.
Sound power from terminals is tested to ISO 5135:2020, which covers air terminal devices, air terminal units, dampers and valves and uses a reverberation room. ANSI/ASHRAE 70, now in its 2023 edition, sets laboratory test methods for air outlets and inlets, covering airflow performance and sound generation. If your specification names either standard, write it on the schedule. We do not publish noise or throw data on the product pages, so we confirm on the quotation what can be offered for your requirement rather than assume it.
Pressure drop
Pressure drop across the terminal adds to what the fan has to overcome, and a damper behind the face adds more. It rises with airflow, and a smaller neck for the same airflow means higher velocity, more pressure drop and more noise. Selecting a size up is often the quiet fix. Give us the airflow per terminal, or the design pressure limit if there is one, so a size can be checked against it.
What to send us to quote
Send one row per terminal type and size. The table shows the columns we need.
Add the airflow per terminal, any throw, NC or NR requirement, the delivery port, and whether the goods ship alone or with a machine order. Quantity is quoted per order, and if you buy by stage or monthly, give that figure too. There is no price list, because the price depends on type, size, material, finish and quantity on each line.
Common mistakes
- Writing a size without saying whether it is the neck or the face.
- Leaving out the duty, so supply and return grilles are mixed up.
- Naming a colour on the drawing but not on the order.
- Giving a throw distance with no terminal velocity, or an NC or NR limit with no airflow.
- Forgetting the damper behind the face until the ceiling void is too shallow.
Send your terminal schedule for a quote →
Taokron supplies these grilles, diffusers and valves. Catalogue figures are confirmed on the quotation for your order.
FAQ
What do I send to get grilles and diffusers quoted?
Your schedule or take-off as a list, Excel, PDF or a photo of the drawing schedule. For each line give the tag, type, size (and whether it is the neck size or the face size), quantity, material, finish and colour, and the duty: supply, return or exhaust. Add the delivery port and whether the goods ship alone or with a machine order.
Which air terminals are in the Taokron range?
Square and rectangular ceiling diffusers (1, 2, 3 or 4-way, in aluminium or stainless steel), supply air grilles with adjustable blades, eggcrate return grilles, round supply and exhaust air valves, opposed blade dampers and square-to-round adapters.
Can you make non-standard sizes?
Diffusers and grilles are made to the size on your schedule. Write width x height and the quantity per size.
Can the diffuser be set after the ceiling is closed?
Yes. The inner cone and vanes come out of the frame, so the throw direction and volume can be set after installation.
Do you publish noise or throw data?
Not on the product pages. If your specification gives a throw distance or a room noise limit, put it on the schedule and we confirm on the quotation what can be offered. Throw, NC and NR describe how a terminal is selected and rated, not what a given item achieves.
Is there a price list for grilles and diffusers?
No. Each line is quoted from your schedule by type, size, material and quantity, and the quotation is per order quantity.